3 General Construction

3.2  Design criteria 

3.2.1 Conventional design


Buildings and structures, and all parts thereof, shall be constructed to support safely all loads, including dead loads.

Where different construction methods and structural materials are used for various portions of a building, the applicable requirements of this part for each portion shall apply. 

3.2.1.1 Conventional building

Conventional construction shall be considered as building with acceptable shape of the figures A2-1 (a to c)   “1 and 2 level house type”. All conventional construction shall be designed in accordance with this code.

3.2.1.2 Irregular building

Irregular buildings shall have an engineered lateral-force resisting system designed in accordance with accepted engineering practice.

A building shall be considered to be irregular when one or more of the following conditions occur:  

a) When exterior shear panels or reinforced frame is not in one plane vertically from the foundation to the uppermost story in which they are required. (See Framed structure)  

b) When a section of floor or roof is not laterally supported by shear panel or reinforced frame on all edges.  

c) When an opening in a floor or roof exceeds the lesser of 3.60m or 50% of the least floors or roofs dimension.  

d) When portions of a floor level are vertically offset.  

e) When shear panel or reinforced frame is do not occur in two perpendicular directions.  

f) When shear panel or reinforced frame are constructed of dissimilar bracing systems on any one-story level above grade. 3.2.1.3  Limit of this code. When a building of otherwise conventional construction contains structural elements, which exceed the limits of this code, those elements shall be designed in accordance with accepted engineering practice.

Fig A2-2 Trinidad & Tobago winds

3.2.2  Engineered design.  

3.2.2.1 General


Buildings shall be constructed in accordance with the provisions of this code as limited by the provisions of this section.
 

3.2.2.2 Wind design.


The requirements in this document are based on design wind speed over open water at equivalent elevation of 10m average over 10 minutes with a recurrence of one in 50 year. (See figure A2-2 Trinidad and Tobago Winds) 

Table 1 Design pressure for winds

Design pressure

 

Trinidad

Central

Trinidad

Coastal

Tobago

Basic wind speed

Km/hr

 

72

 

92

 

101

 

Wall (horizontal load) kN/m2

 

0.70

 

0.90

 

1.00

 

Roof (uplift) kN/m2

 

1.00

 

1.30

 

1.45


3.2.2.3  Seismic design.

All buildings shall be constructed in accordance with the provisions of this section. 


3.2.2.3.1 Seismic design category.

3.2.2.3.1.1  Ground acceleration
The requirements in this document are based on maximum ground acceleration associated with 10% probability of occurrence in 50 years. For Trinidad & Tobago 0.3 g (g refers to the gravity and g = 9.81m/s2)  
3.2.2.3.1.2  Amplification factor
Where the soil is 100% saturated (low land, reclaimed land, etc.) an amplification factor of 2 shall be applied to the ground acceleration.  See calculation for shear load.  
3.2.2.3.1.3  Soil liquefaction
To prevent any soil liquefaction on the same type of land than above a special attention shall be carried out with an engineer specialist for the choice of the appropriate type of foundation. See calculation for shear load.
  3.2.2.3.2 Weights of applied finishes Dead load finishes shall not exceed 1 kN/m2 for roofs or 0.5 kN/m2 for floors.  Dead load finishes for walls above grade shall not exceed: a- light-frame walls 0.75 kN/m2 for exterior 0.50 kN/m2 for interior b- masonry walls. 2.50 kN/m2 for 150mm thick masonry wall. 3.80 kN/m2 for 200 mm thick masonry wall. c- concrete walls. 4.10 kN/m2 for 150 mm thick concrete walls. 3.2.2.3.3 Height limitations.  The design applied to any construction is limited to two stories with a maximum of 9m to the top of the building.

3.2.2.4 Flood plain construction.            

Buildings and structures constructed in flood prone areas as established in Fig. A2-1 shall be designed and constructed in accordance with Clause Flood resistant construction and Clause Coastal high hazard areas of Part "Minimal requirements".
  

3.2.3 Dead load. 
            

The actual weights of materials and construction shall be used for determining dead load with consideration for the dead load of fixed service equipment.

3.2.4 Live load. 

The minimum uniformly distributed live load shall be as provided in Table 2.

Table 2 Minimum uniformly distributed live loads
Use Live loads (kN/m2)
Exterior balconies 5
Domestic floor / All rooms, stairs and corridors 1.5
Office floor 2.5
Small industrial and storage 5
Use Horizontal loads (kN/m)
Guard rails and handrails 1


Fig A2-3 Trinidad flood prone areas

3.2.5 Roof load

Roof shall be designed for the live load indicated in Table 3.

Table 3 Minimum roof live loads (kN/m2)

    Roof slope

Tributary loaded area for any structural members

Area (m2)

0 to 20m2

20 to 55m2

over 55m2

Flat or rise less than (20°) 33% slope

1

0.75

0.6

Rise (20°) 33% to (45°) 100%

0.75

0.7

0.6

Rise greater than (45°) 100%

0.6

0.6

0.6

    

 



 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 


3.2.6 Lateral load design  

3.2.6.1            

Preamble
Wind and earthquake introduce horizontal loads in the superstructure that are transferred to the foundation. We have to consider 2 steps: a) Transfer of the horizontal load from - wind to vertical wall and roof - acceleration of mass located everywhere in the superstructure to the appropriated wall or framed structure. b) Transfer of the load from the top to the bottom of the wall or superstructure and the foundation. According to this code - horizontal transfer is done by horizontal diaphragm or horizontal beam - vertical transfer is one by shear panel, cross, or framed structure   3.2.6.2  Diaphragm Floor, roof or ceiling assemblies may be constructed with the necessary stiffness and load path continuity to distribute lateral loads (wind and earthquake) to lateral support subsystems. In this role, floor, roof or ceiling surface act as horizontal beams (also called a diaphragm) spanning lateral supports points. Use of floor, roof or ceiling assembly, as a diaphragm requires both strength and stiffness properties and development of connections to transfer the diaphragm force.



Fig B6-2 Shear panel - Horizontal core blocks

3.2.6.3 Shear panel
  

3.2.6.3.1  

Concrete wall
A shear panel (see figures B-6-1 and B-6-2 Shear panel) is a portion or section of a 150mm exterior wall that performs the function of resisting lateral earthquake or wind forces. 3.2.6.3.2  Timber See paragraph "Wall bracing".   

3.2.7 Load factors.

All structures shall resist combined loads as follows;
  

3.2.7.1            

Gravity
1.40 D + 1.70 L 3.2.7.2            
Earthquake
  a) 0.75 (1.40 D + 1.70 L +/- 1.87 E) and b) 0.90 D +/- 1.43 E   3.2.7.2.1           
Shear load calculation
            

A simplified formula, for this code is
  V =  0.05 x S x W  total shear in kN  Whereas : The 0.05 coefficient integrated the Z = ground acceleration, C = amplification factor due to structure frequency, I = Importance factor =1 in this code and Rw  = Ductility factor related with respect to the column design reinforcement used in the normal practice formula.   S = site factor S = 1    For good soil (rock, gravel) S = 1.2 For softer material (clay, fill ) S = 1.5 For deep alluvial deposits S = 2.5 maximum for reclaimed land and saturated soils (due to the amplification factor)   W = total load in kN 

3.2.7.3            

Wind
1.40 D + 1.70 L + 1.75 W   Note: D = dead load L = live load E = earthquake load W = wind load   

3.2.8 Deflection. 
            

The allowed deflection of any structural member under the live load shall not exceed the following values in Table 4
Table 4 – Maximum deflection authorised.

Rafters and purlins                                       

L/180

Interior walls and partitions

H/180  

Floors and ceilings

L/360  

All others structural members

L/240  

  NOTES: L = span length             H = span height